Schneider Electric Circuit breaker NG125H, 3-pole, 80A, 18731
Product details
Schneider Electric Circuit Breaker 18731
Manufacturer: Schneider Electric
Designation: Circuit Breaker 3p 80A C NGH125H
Type: 18731
Installation Depth: 47 mm
Tripping Characteristic: C
Number of Poles (total): 3
Number of Protected Poles: 3
Rated Current: 80 A
Rated Voltage: 415 V
Rated Insulation Voltage Ui: 690 V
Rated Impulse Voltage Uimp: 8 kV
Voltage Type: AC/DC
Rated Breaking Capacity Icu according to IEC 60947-2 at 230 V: 70 kA
Rated Breaking Capacity Icu according to IEC 60947-2 at 400 V: 36 kA
Frequency: 50..60 Hz
Flush Mounting: no
Switching Neutral Conductor: no
Overvoltage Category: 4
Pollution Degree: 3
Additional Devices Possible: yes
Width in Division Units: 4.5
Protection Class (IP): IP20
Ambient Temperature during Operation: -30..70 °C
Connectable Conductor Cross-Section Multi-Wire: 10..50 mm²
Connectable Conductor Cross-Section Single-Wire: 16..70 mm²
Explosion-Proof: no
Schneider Electric Circuit Breaker 18731: Additional Details
Acti 9 NG125H Circuit Breaker, 36kA (IEC/EN 60947-2). 2-pole, rated current 63A, C characteristic, operating voltage (Ue) 380-415V AC, insulation voltage (Ui) 690V AC. Protects the circuit against short-circuit currents and overload currents. The tripping is indicated by the middle position of the switch lever and a red mechanical indicator on the front of the device. Test button to check the tripping mechanism. Feed-in from the top or bottom. Jump switching for low-wear contact switching. Tripping Unit Technology: thermomagnetic. Additional snap-on auxiliary modules (optional): indication of switching position, fault tripping, working current tripping, undervoltage tripping, overvoltage tripping. The NG125H circuit breaker complies with the following standards: IEC/EN 60947-2. Furthermore, this series is VDE certified.
Circuit breaker type | Circuit breaker |
Mounting type | Flush-mounted |
number of poles | 3 |
Length | 47 mm |
Item number | 23347893 |
Manufacturer | Schneider Electric |
Category | Residual-current device |
Manufacturer No. | 18731 |
Release date | 7-12-2022 |
External links |
Circuit breaker type | Circuit breaker |
Mounting type | Flush-mounted |
number of poles | 3 |
Tripping characteristic | C |
Rated current | 80 A |
Rated voltage | 415 V |
voltage type | AC/DC |
Insulation voltage (Ui) | 690 V |
Protection type (IP code) | IP20 |
Country of origin | France |
Manufacturer commitment | RE100, SBTi |
CO₂ emissions | 29,26 kg |
Climate contribution | EUR 0,75 |
Items per sales unit | 1 pcs. |
Length | 47 mm |
Product Safety |
30-day right of return
Compare products
Goes with
Reviews & Ratings
Statutory warranty score
How often does a product of this brand in the «Residual-current device» category have a defect within the first 24 months?
Source: Galaxus- 1.Siemens0 %
- 5.ABB0,1 %
- 5.Schneider Electric0,1 %
- 7.Hager0,3 %
- 8.Steffen0,4 %
Statutory warranty case duration
How many working days on average does it take to process a warranty claim from when it arrives at the service centre until it’s back with the customer?
Source: Galaxus- ABBNot enough data
- BrennenstuhlNot enough data
- EatonNot enough data
- HagerNot enough data
- Max HauriNot enough data
Unfortunately, we don't have enough data for this category yet.
Return rate
How often is a product of this brand in the «Residual-current device» category returned?
Source: Galaxus- 2.Steffen0,6 %
- 3.Eaton0,7 %
- 4.Schneider Electric1,6 %
- 5.ABB3 %
- 5.Siemens3 %